The **JR28-R-4LDP2** is a specific model of a **Thermal Overload Relay**, commonly used in industrial automation to protect electric motors from overheating, phase failure, and overcurrent conditions. It is typically designed to be compatible with LC1-D series contactors.
---
## 1. Core Technical Specifications
The following table outlines the primary electronic and mechanical characteristics:
| Feature | Specification |
| :--- | :--- |
| **Relay Type** | Thermal Overload |
| **Model Series** | JR28 (Compatible with LR2-D) |
| **Current Setting Range** | Typically 23A - 32A (Verify on unit) |
| **Auxiliary Contacts** | 1 NO (Normally Open) + 1 NC (Normally Closed) |
| **Rated Voltage (Ue)** | Up to 690V AC |
| **Tripping Class** | 10A (Standard protection) |
| **Reset Mode** | Manual or Automatic |
---
## 2. Key Electronic Components & Functions
### A. Bimetallic Elements
The heart of the JR28 is the **bimetallic strip**.
* **Function:** As current flows through these strips, they heat up. Because the strips consist of two different metals with different expansion rates, they bend when heated.
* **Protection:** If the current exceeds the set threshold for a specific duration, the physical bending triggers a mechanical linkage that opens the control circuit.
### B. Auxiliary Contacts (1NO + 1NC)
These are the electronic signal terminals used for control logic:
* **NC (95-96):** Connected in series with the contactor coil. It opens during a fault, cutting power to the motor.
* **NO (97-98):** Closes during a fault. Usually connected to an indicator light or an alarm to notify the operator of a trip.
### C. Phase Failure Protection
The JR28-R includes a differential mechanism. If one phase loses current while others are under load, the relay trips faster than a standard overcurrent event to prevent "single-phasing," which quickly destroys motor windings.
---
## 3. Physical Interface & Controls
1. **Current Adjustment Dial:** A rotary pot on the front allows the user to set the exact Amperage corresponding to the motor's Full Load Amps (FLA).
2. **Test Button:** Manually simulates a trip to verify that the auxiliary contacts (95-98) are functioning correctly.
3. **Reset Button:** A blue button used to restore the circuit after a trip has occurred (once the bimetal has cooled).
4. **Stop Button:** A red button that manually opens the NC contact to test the control circuit stop function.
---
## 4. Wiring Diagram Concept
```text
[Main Power L1, L2, L3]
|
[Contactor (LC1-D)]
|
[JR28-R-4LDP2 (Overload Relay)] ----> [97-98: Alarm/Light]
| ----> [95-96: Series with Coil]
[Electric Motor]
```
---
- ⤷