The **LPS-RK-100SPI** is a high-performance, time-delay power fuse belonging to the **Low-Peak™** series manufactured by Bussmann (Eaton). It is specifically designed for circuit protection in industrial and commercial applications.
---
## 1. Core Technical Specifications
The electrical characteristics define how the part reacts under load and fault conditions.
| Specification | Value |
| :--- | :--- |
| **Current Rating** | 100 Amps |
| **Voltage Rating (AC)** | 600 Vac |
| **Voltage Rating (DC)** | 300 Vdc |
| **Interrupting Rating (AC)** | 300,000 Amps RMS Symmetrical |
| **Interrupting Rating (DC)** | 100,000 Amps |
| **Fuse Class** | Class RK1 |
| **Type** | Dual-Element, Time-Delay |
---
## 2. Key Electronic Features
### Dual-Element Design
The "RK-100" utilizes a dual-element construction. This allows the fuse to distinguish between temporary power surges and harmful overloads:
* **Thermal Element:** Handles low-level overloads (like motor startup currents) without blowing.
* **Magnetic/Short-Circuit Element:** Reacts almost instantaneously to high-magnitude short circuits.
### The "SPI" Indicator
The **SPI** suffix stands for **Smart Presence Indicator**.
* It features a permanent visual trigger (usually a neon lamp or mechanical indicator) that signals when the fuse has opened.
* This significantly reduces troubleshooting time in large electrical panels.
### Current Limitation
As a **Class RK1** fuse, it is highly current-limiting. In the event of a short circuit, it interrupts the current before it reaches its peak value, protecting downstream components (like contactors or breakers) from mechanical and thermal stress.
---
## 3. Physical Construction
The fuse is built to withstand harsh industrial environments:
* **Body Material:** High-grade fiberglass or melamine tube for superior arc quenching.
* **End Caps:** Blade-style terminals (standard for 100A RK1 frames) made of high-conductivity copper alloy, typically tin-plated to prevent oxidation.
* **Rejection Feature:** The RK1 physical design prevents the installation of lower-rated fuses (like Class H or K) into the same fuse holder, ensuring safety standards are maintained.
---
## 4. Common Applications
Due to its 100A rating and time-delay characteristics, it is primarily used for:
1. **Motor Branch Circuits:** Accommodates high inrush currents during motor startup.
2. **Transformer Protection:** Resists nuisance blowing during transformer energization.
3. **Main Panelboards:** Provides high-capacity protection for industrial distribution systems.
- ⤷