LPS-RK-60SP
AI

The **LPS-RK-60SP** is a high-performance, current-limiting, dual-element time-delay fuse. It belongs to the **Low-Peak™** series manufactured by Bussmann (Eaton). This specific model is rated for **60 Amps** and is designed for power distribution and motor protection.
---
### Technical Specifications
| Feature | Specification |
| :--- | :--- |
| **Part Number** | LPS-RK-60SP |
| **Amperage Rating** | 60A |
| **Voltage Rating (AC)** | 600 Vac |
| **Voltage Rating (DC)** | 300 Vdc |
| **Interrupting Rating (IR)** | 300kA RMS Sym. (AC) / 100kA (DC) |
| **Fuse Class** | Class RK1 |
| **Design Type** | Dual-Element, Time-Delay |
| **Body Material** | Melamine glass tube with brass endcaps |
---
### Key Electronic & Functional Characteristics
#### 1. Dual-Element Design
The fuse contains two distinct components working in series:
* **Thermal Element:** Handles low-level overloads. It provides a "time-delay" (typically 10 seconds at 500% of the rated current) to prevent nuisance tripping caused by motor startup currents.
* **Magnetic/Short-Circuit Element:** A fast-acting component that triggers instantly if a high-magnitude short circuit occurs.
#### 2. High Current Limitation
As a **Class RK1** fuse, the LPS-RK-60SP is significantly more current-limiting than Class RK5 fuses. It limits the "peak let-through" current during a fault, which protects downstream components (like contactors and breakers) from thermal and magnetic stress.
#### 3. High Interrupting Rating
With a **300kA** interrupting rating, this fuse can safely extinguish very high-energy arcs, making it suitable for systems with high available fault currents.
---
### Applications
* **Motor Branch Circuits:** Ideal for motors with high inrush currents.
* **Inductive Loads:** Transformers and solenoids.
* **Panelboards:** Used as a main or branch fuse in power distribution centers.
* **General Purpose:** Protection of non-inductive loads where high-level short-circuit protection is required.
---
### Comparison: RK1 vs. RK5
| Feature | Class RK1 (LPS-RK) | Class RK5 (FRN-R / FRS-R) |
| :--- | :--- | :--- |
| **Protection Level** | Superior (Higher Limitation) | Standard |
| **Let-through Energy** | Very Low | Moderate |
| **Interchangeability** | Fits same holders as RK5 | Fits same holders as RK1 |
- ⤷
What is the difference between a time-delay and a fast-acting fuse?
- ⤷ Can an LPS-RK-60SP fuse be used in a 240V circuit?
- ⤷ What are the physical dimensions of a Class RK1 60A fuse?