M2UDS-DE-R
AI

The **M2UDS-DE-R** is a specific model within the **M2UDS Series** of digital capacitive level switches manufactured by **Nohken**. These devices are primarily used for point level detection of powders, granules, and liquids.
Below is a detailed breakdown of its electronic components, specifications, and technical features.
---
## 1. Technical Specifications
The "DE" suffix typically denotes a specific configuration regarding output and power supply.
| Feature | Specification |
| :--- | :--- |
| **Detection Method** | Capacitive (Admittance) |
| **Power Supply** | 20 to 250V AC/DC (Universal) |
| **Output Type** | Relay Contact (SPDT) |
| **Contact Capacity** | 250V AC 5A / 30V DC 5A (Resistive load) |
| **Power Consumption** | Approx. 2W / 5VA |
| **Operating Temp** | -20°C to +60°C (Electronic insert) |
| **Sensitivity Range** | 0.5pF to 20pF (Adjustable) |
---
## 2. Core Electronic Components
The internal circuitry is divided into three functional blocks:
### A. Sensing Circuit (The Probe)
The probe acts as one plate of a capacitor. When the medium (material) touches the probe, the capacitance changes relative to the ground (tank wall).
* **Guard Circuit:** Often includes a "Shield" or "Guard" section to prevent false triggering caused by material buildup or coating on the probe.
### B. Signal Processing Unit
* **Oscillator:** Generates a high-frequency signal to detect impedance changes.
* **Comparator/Microprocessor:** Compares the measured capacitance against a pre-set threshold (Sensitivity).
* **Delay Timer:** Integrated electronics usually include a "Time Delay" (typically 0–10 seconds) to prevent "chattering" caused by turbulent liquids or falling material.
### C. Output Module
* **Relay (R):** The "R" in the model name stands for **Relay**. It provides a dry contact output.
* **Fail-Safe Switch:** A physical slide switch on the PCB that allows the user to select **HLFS** (High Level Fail-Safe) or **LLFS** (Low Level Fail-Safe).
---
## 3. Wiring and Terminals
The electronic base features a terminal block for field wiring.
| Terminal No. | Function | Description |
| :--- | :--- | :--- |
| 1 & 2 | Power Input | 20-250V AC/DC (Non-polarized) |
| 3 | COM | Common Relay Contact |
| 4 | NC | Normally Closed Contact |
| 5 | NO | Normally Open Contact |
| E | Ground | Connection to tank/Earth |
---
## 4. Operational Indicators
The M2UDS electronics include LED indicators for real-time diagnostics:
1. **Green LED (Power):** Indicates the unit is energized.
2. **Red LED (Status):** Indicates the relay is energized (Material detected or Fail-safe state).
3. **Sensitivity Potentiometer:** A multi-turn trimmer used to calibrate the device based on the dielectric constant of the material being measured.
---
- ⤷How do you calibrate the sensitivity for low-dielectric materials like plastic pellets?
- ⤷ What is the difference between the M2UDS-DE-R and the M2UDS-DE-T (Transistor) models?
- ⤷ How does the build-up suppression (Guard) circuit work in this model?