M2VS-AA-R2SLASHCE
AI

The **M2VS-AA-R2/CE** is an ultra-slim, signal conditioner (isolator) manufactured by **M-System**. It is designed to convert an analog input signal into a standard analog output signal while providing galvanic isolation between the input, output, and power supply.
### 1. General Specifications
| Feature | Description |
| :--- | :--- |
| **Model Series** | M2V Series (Ultra-slim signal conditioners) |
| **Input Signal** | 4 – 20 mA DC |
| **Output Signal** | 4 – 20 mA DC |
| **Power Supply** | 24V DC |
| **Isolation** | 3-way isolation (Input to Output to Power) |
| **Standards** | CE Marking certified |
---
### 2. Breakdown of the Model Number
The suffix **M2VS-AA-R2/CE** follows a specific nomenclature:
* **M2VS**: The model type (Voltage/Current Input Signal Conditioner).
* **A (First A)**: Input Code (4 – 20 mA DC).
* **A (Second A)**: Output Code (4 – 20 mA DC).
* **R2**: Power Input (24V DC).
* **CE**: Confirms compliance with European safety and EMC standards.
---
### 3. Electronic Components & Features
#### A. Signal Isolation & Protection
* **Galvanic Isolation:** Uses internal optoisolators or transformers to break the ground loop, preventing noise from traveling from the field devices to the PLC/DCS.
* **Dielectric Strength:** Usually rated for 2000V AC @ 1 minute.
#### B. Precision Circuitry
* **Operational Amplifiers:** High-precision op-amps ensure a linear transfer function between the input and output.
* **Zero/Span Adjustments:** Located on the front panel, these allow for fine-tuning the electronic calibration (usually ±5%).
#### C. Physical Construction
* **Housing:** Flame-resistant resin (Black).
* **Mounting:** DIN Rail mounting.
* **Terminals:** M3 screw terminals for secure electronic connections.
---
### 4. Technical Performance Data
| Parameter | Value |
| :--- | :--- |
| **Accuracy** | ±0.1% |
| **Temperature Coefficient** | ±0.015% per °C |
| **Response Time** | ≤ 0.5 seconds (0 – 90%) |
| **Insulation Resistance** | ≥ 100 MΩ with 500V DC |
| **Load Resistance** | Up to 550 Ω |
---
### 5. Application Circuit Example
Typically, this device is used in industrial automation environments:
1. **Input Side:** Connected to a 2-wire or 4-wire transmitter (e.g., Pressure or Temperature sensor).
2. **Output Side:** Connected to an Analog Input card of a PLC.
3. **Function:** It protects the PLC from high-voltage surges and eliminates ground loop interference which can cause signal inaccuracies.
- ⤷
What is the difference between the M2VS and the M2RS series?
- ⤷ How do you calibrate the Zero and Span on this specific model?