RXM2AB2B7PVM
AI

The **RXM2AB2B7PVM** is a pre-assembled electromechanical relay kit from the Zelio Relay range, manufactured by Schneider Electric. This specific part number refers to a combination of a miniature plug-in relay and its corresponding socket.
---
## 1. Component Breakdown
The part number represents a complete package consisting of two primary electronic sub-components:
| Component | Description |
| :--- | :--- |
| **Relay (RXM2AB2B7)** | The electromechanical switching device. |
| **Socket (RXZE2M114)** | The base used for DIN rail mounting and wiring connections. |
---
## 2. Key Technical Specifications
The electronic behavior of this part is defined by its coil requirements and contact ratings.
### Coil Characteristics (Input)
* **Control Circuit Voltage:** 24 V AC.
* **Frequency:** 50/60 Hz.
* **Average Consumption:** 1.2 VA (AC).
* **Drop-out Voltage Threshold:** $\ge$ 0.15 Uc (Input voltage).
### Contact Characteristics (Output)
* **Contact Type:** 2 C/O (Changeover / DPDT - Double Pole Double Throw).
* **Conventional Enclosed Thermal Current ($I_{th}$):** 12 A.
* **Maximum Switching Voltage:** 250 V AC / 28 V DC.
* **Maximum Switching Capacity:** 3000 VA (Resistive load).
* **Minimum Switching Capacity:** 170 mW at 10 mA, 17 V.
---
## 3. Electronic Features & Indicators
This relay includes specific electronic and mechanical diagnostic tools to aid in troubleshooting:
1. **Mechanical Flag Indicator:** A small orange window that physically moves to show if the relay is energized.
2. **Status LED:** A built-in Green LED that illuminates when the coil is receiving power.
3. **Manual Test Button:** A turquoise push-button that allows a technician to manually force the contacts to change state without power, useful for testing circuit continuity.
4. **Removable Lock-down Door:** Allows the test button to be locked in the "on" position for maintenance.
---
## 4. Wiring and Pin Configuration
The device uses a standard pin layout for miniature relays:
```text
(Contact Layout)
Pin 13 & 14: Coil Connections (A1, A2)
Pin 9 & 12: Common (COM)
Pin 1 & 4: Normally Closed (NC)
Pin 5 & 8: Normally Open (NO)
```
---
## 5. Usage Environment
* **Mechanical Durability:** 10,000,000 cycles.
* **Electrical Durability:** 100,000 cycles (for resistive loads).
* **Operating Temperature:** -40°C to 55°C.
* **Protection:** IP20 (Finger safe).
- ⤷
What is the difference between this 24V AC version and a 24V DC version of the same relay?
- ⤷ Can this relay be used to switch inductive loads like motors
- ⤷ and what are the derating factors?
- ⤷ How does the manual test button lock-down mechanism work for long-term testing?