26 / 36 page ![]() 26 Enter the probe burn-out action. In the event of a temperature probe failure, the alarm output can be programmed to go on or off. SETPOINT ANNUNCIATORS PROBE BURN-OUT ACTION (PAXT ONLY) Alternate Setpoints An Alternate list of setpoint values can be stored and recalled as needed. The Alternate list allows an additional set of setpoint values. (The setpoint numbers nor rear terminal numbers will change in the Alternate list.) The Alternate list can only be activated through a function key or user input programmed for in Module 2. When the Alternate list is selected, the Main list is stored and becomes inactive. When changing between Main and Alternate, the alarm state of Auto Reset Action alarms will always follow their new value. Latched “on” alarms will always stay latched during the transition and can only be reset with a user input or function key. Only during the function key or user input transition does the display indicate which list is being used. ALARM STATE OFF ON Hys SP OFF ON OFF OFF ON OFF ON OFF OFF ON OFF ON OFF MANUAL RESET SP - Hys ( Auto) (LAtC1) (LAtC2) ì í î Setpoint Alarm Reset Actions The mode disables display setpoint annunciators. The mode displays the corresponding setpoint annunciators of “on” alarm outputs. The mode displays the corresponding setpoint annunciators of “off” alarms outputs. The mode flashes the corresponding setpoint annunciators of “on” alarm outputs. 7-SrL dAtA Baud Rate bAUd Parity Bit PAr Print Total Value tot Addr Meter Address Abrv Abbreviated Printing Print Input Value INP SPNt HILO PAR Pro Data Bit Print Max & Min Values Print Setpoint Values OPt Print Options 6roSS Gross tArE Tare PAXS ONLY PAXS ONLY 6.7 mOdUle 7 - serial COmmUniCaTiOns parameTers () Ñ PARAMETER MENU DATA BIT BAUD RATE Set the baud rate to match that of other serial communications equipment. Normally, the baud rate is set to the highest value that all of the serial communications equipment is capable of transmitting. Select either 7 or 8 bit data word lengths. Set the word length to match that of other serial communication equipment. Since the meter receives and transmits 7-bit ASCII encoded data, 7 bit word length is sufficient to request and receive data from the meter. Ñ - A communication card must be installed in order to access this module. PARITY BIT Set the parity bit to match that of the other serial communications equipment used. The meter ignores the parity when receiving data, and sets the parity bit for outgoing data. If no parity is selected with 7-bit word length the meter transmits and receives data with 2 stop bits. (For example: 10 bit frame with mark parity) METER ADDRESS to Enter the serial node address. With a single unit on a bus, an address is not needed and a value of zero can be used (RS232 applications). Otherwise, with multiple bussed units, a unique address number must be assigned to each meter. The node address applies specifically to RS485 applications. |
|
Link URL |
| Lei ha avuto il aiuto da alldatasheet? [ DONATE ] |
Di alldatasheet | Richest di pubblicita | contatti | Privacy Policy | Collegamento alla scheda tecnica | scambio Link | Ricerca produttore All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |